Jäger J, Braisch D, Ramold M, Li S, Krebs R (2005)
Publication Type: Conference contribution
Publication year: 2005
Edited Volumes: 2005 IEEE Russia Power Tech, PowerTech
Pages Range: Report 219
Conference Proceedings Title: 2005 IEEE St. Petersburg PowerTech
Event location: St. Petersburg (Russland)
The presented paper is dealing with protection principles which are preferable applied to networks with distributed generation (DG). A basic physical explanation of the high-impedance protection principle in relation to the low-impedance principle will be given considering the transient behaviour in particular. It can be shown that special requirements on the protection co-ordination for networks with DG can be covered by the high-impedance protection principle. Measurement results of a high current lab confirm the favourable behaviour of the high-impedance protection principle. It was also possible to investigate the transient behaviour of the high-impedance principle under extreme conditions like CT remanence effects. A close correlation between digital simulation and measurement results of the transient behaviour could be achieved during the investigations.
APA:
Jäger, J., Braisch, D., Ramold, M., Li, S., & Krebs, R. (2005). Transient Behaviour of High Impedance Protection Applications using for Networks with Distributed Generation. In 2005 IEEE St. Petersburg PowerTech (pp. Report 219). St. Petersburg (Russland).
MLA:
Jäger, Johann, et al. "Transient Behaviour of High Impedance Protection Applications using for Networks with Distributed Generation." Proceedings of the 2005 IEEE St. Petersburg PowerTech, St. Petersburg (Russland) 2005. Report 219.
BibTeX: Download